Burner Equipments
Burner Controller
Sequences ignition, proving and safety interlocks into one supervised start-up.
Product view
Flame Sensors
The BC-F range covers both flame-proving principles: ionisation probes for stable gas flames with a good earth path, and UV cells for larger flames, dual-fuel duty or where a probe cannot be positioned reliably. Either way the controller sees a real, continuous signal from a real flame — not an assumption that ignition succeeded.
Confirmed against your duty at order stage — send us the operating conditions and we will verify the selection.
| Parameter | Value |
|---|---|
| Detection method | Ionisation probe or UV cell |
| Response time | < 1 s flame-failure detection |
| Service temperature | Up to +600 °C (probe tip) |
| Enclosure | IP54 |
| Cable | Screened, heat-resistant |
| Operating temperature | −20 °C to +60 °C |
Datasheets, installation manuals, drawings and conformity declarations.
Documentation for Flame Sensors is issued on request against the confirmed specification. Request the document pack.

Burner Equipments
Sequences ignition, proving and safety interlocks into one supervised start-up.

Burner Equipments
Drives the air and gas dampers that hold combustion ratio across the firing range.

Gas Pressure Regulators
Direct-acting, spring-loaded regulation with threaded connections, rated PS 16 bar.
The more detail you give on the duty, the more precise the proposal comes back.
What engineers most often ask when specifying this equipment.
Ionisation probes are simpler and cheaper and work well on stable, well-defined gas flames with a good earth path. UV cells suit larger flames, oil/gas dual-fuel duty and installations where the probe cannot be positioned reliably.