Gas Pressure Regulators
R Series – Gas Pressure Regulator, Threaded Connection PS: 16 bar
Direct-acting, spring-loaded regulation with threaded connections, rated PS 16 bar.
Product view
Low Pressure Regulators
The GR-L handles the last step before the burner or appliance, delivering a stable millibar-range outlet from a low or medium-pressure feed. A large diaphragm area relative to the seat gives the sensitivity that low-pressure duties demand, and a compact body keeps it viable inside plant rooms and appliance enclosures.
Confirmed against your duty at order stage — send us the operating conditions and we will verify the selection.
| Parameter | Value |
|---|---|
| Inlet pressure | Up to 5 bar |
| Outlet pressure | 8 – 300 mbar |
| Sizes | DN 15 – DN 80 |
| Accuracy class | AC 5 – AC 10 |
| Lock-up class | SG 10 – SG 20 |
| Connections | Threaded BSP / NPT |
| Body material | Aluminium alloy |
| Temperature range | −20 °C to +60 °C |
Datasheets, installation manuals, drawings and conformity declarations.
Documentation for Low Pressure Regulators is issued on request against the confirmed specification. Request the document pack.

Gas Pressure Regulators
Direct-acting, spring-loaded regulation with threaded connections, rated PS 16 bar.

Gas Pressure Regulators
Direct-acting, spring-loaded regulation with flanged connections, rated PS 25 bar.

Gas Pressure Regulators
Tight accuracy at high capacity, using the gas stream itself as the control amplifier.
The more detail you give on the duty, the more precise the proposal comes back.
What engineers most often ask when specifying this equipment.
Spring-loaded units are simpler, cheaper and ideal where flow is modest and a few percent of droop is acceptable. Pilot-operated units use the gas itself to amplify the control signal, giving far tighter accuracy at high capacity — the usual choice above roughly DN 50 or where accuracy class AC 1–2.5 is specified.